TECHNICAL CALCULATOR

Generator Sizing Calculator

Estimate standby generator capacity based on connected load, power factor, motor starting allowance, diversity and future expansion.

Standby Power Estimator

Calculate Recommended Generator Capacity

Technical Notes

Generator Sizing Considerations

Motor starting currents can significantly affect generator sizing

Generator loading should avoid long-term underloading

Altitude and temperature can derate generator capacity

UPS and inverter loads may affect generator performance

Final sizing should be based on site-specific load assessment

Worked Example

Typical Generator Sizing Example

Example Inputs

Connected Load
100kW
Diversity
80%
Motor Starting Allowance
25%
Future Expansion
20%
Target Loading
80%

Calculated Result

Diversified load
80kW
Motor allowance
20kW
Expansion allowance
16kW
Required load
116kW
Recommended generator
145kW

Suggested generator size: approximately 200kVA depending on power factor and manufacturer rating.