UPS Load Calculator

Build a connected equipment list and estimate total kW, kVA, current and recommended UPS capacity.

Connected Equipment Planning

Estimate UPS load before selecting equipment.

Use this tool for early-stage sizing when a site needs to back up PCs, servers, switches, routers, screens and office equipment.

Equipment Load Inputs

Build your connected equipment list.

Load item 1

Load item 2

Load item 3

Equipment Breakdown

Connected load summary

Largest load item

Server Rack (3 000 W)

Total equipment items

4

EquipmentQtyWatts / ItemDiversityRow Total WRow kVA
Server Rack13 000 W1,003 000 W3,3 kVA
Network Switch2150 W1,00300 W0,3 kVA
Router / Firewall1100 W1,00100 W0,1 kVA

Technical Recommendations

UPS selection guidance

3 kVA

Likely undersized

5 kVA

Recommended

6 kVA

Consider where future expansion is expected

UPS Selection: UPS selection should allow for critical load growth, unknown equipment, startup behaviour and future expansion.
IT Load Note: IT and network loads can change over time. Where possible, confirm the actual load with a power meter or UPS load reading before final design.
UPS Supply Breaker: UPS supply breaker is estimated from selected UPS rating plus a 15% charger/input allowance. Final breaker size must be confirmed against the UPS manufacturer input current, cable size, fault level and site conditions.
Server Room Note: Server and rack loads should be checked against actual measured power usage where possible. Consider A/B power feeds, redundancy, monitoring and cooling.

UPS Load Assessment

Need help confirming your UPS load?

Send your load estimate to Emerald and our team can assist with UPS selection, runtime, battery sizing and electrical distribution.

Request UPS Load Assessment